Ensuring safe operating conditions for power transformers under thermal effects of short-circuit curre
https://doi.org/10.23947/1992-5980-2018-18-1-132-137
Abstract
Introduction. Power transformers are the basic equipment of the industrial power systems. One of the key indicators of determining the service lifetime of the transformer including its performance characteristics is the condition and residual life of its isolation. Aging and f insulation deprecation are directly related to the operating temperature of the transformer in use, as well as to the reliable operation of the cooling system. This research direction is up-to-date, especially when it comes to fully rated power transformers.
Materials and Methods. Power transformers of the district substations that feed the industrial and transport enterprises are considered. Modes of power transformers, which are caused by the uneven workload of the phases and short-circuiting, are studied. All these factors lead to the thermal deformation of the power transformer insulation and, as a rule, to the outage of power transformers.
Research Results. The forced cooling system of power transformers, which allows increasing their cooling capacity and the cooling fluid volume, is developed by the authors and described in the paper. Thermal calculations of heating design elements of the power transformers are carried out both in the conventional cooling system and the new one. The comparative analysis and calculations have shown the feasibility of the developed cooling system of power transformers, which allows extending the insulation lifetime. The developed cooling system is forced. The authors used a reserve power transformer tank as an additional expander. This design solution can be implemented for transformers operating at low temperatures, as well as under long-term limit loads.
Discussion and Conclusions. The developed cooling system eliminates the requirement for purchase costs on extra equipment and maintenance support. It can be used at the enterprise power facilities and in the rail transportation.
About the Authors
A. V. KostyukovRussian Federation
Kostyukov, Alexander V.,associate professor of the Theoretical Basics of Electrical Engineering Department, Cand.Sci. (Eng.)
344038, Rostov-on-Don, Rostovskogo Strelkovogo Polka Narodnogo Opolcheniya sq., 2
V. A. Solomin
Russian Federation
Solomin, Vladimir A.,professor of the Electrical Machines and Devices Department, Dr.Sci. (Eng.), professor
344038, Rostov-on-Don, Rostovskogo Strelkovogo Polka Narodnogo Opolcheniya sq., 2
A. A. Kostyukov
Russian Federation
Kostyukov, Alexander A., postgraduate student of the Electrical Machines and Devices Department
344038, Rostov-on-Don, Rostovskogo Strelkovogo Polka Narodnogo Opolcheniya sq., 2
References
1. Figurnov, E.P. Releynaya zashchita setey tyagovogo elektrosnabzheniya peremennogo toka. [Relay protection of AC traction energy networks.] Moscow: Marshrut, 2006, 272 p. (in Russian).
2. GOST R 51559–2000. Gosudarstvennaya sistema obespecheniya edinstva izmereniy. Transformatory silovye maslyanye klassov napryazheniya 110 i 220 kV i avtotransformatory napryazheniem 27,5 kV dlya elektricheskikh zheleznykh dorog peremennogo toka. [GOST 51559–2000. General-purpose oil-immersed power transformers of 110 and 220 kV and autotransformers of 27.5 kV for electric a.c. railways.] Interstate Council for Standardization, Metrology and Certification (ISC). Moscow: Standartinform, 2000, 13 p. (in Russian).
3. GOST R 52719–2007. Gosudarstvennaya sistema obespecheniya edinstva izmereniy. Transformatory silovye. Obshchie tekhnicheskie usloviya. [GOST R 52719–2007. Power transformers. General specifications.] Interstate Council for Standardization, Metrology and Certification (ISC). Moscow: Standartinform, 2007, 40 p. (in Russian).
4. Tereza, G.P., ed. Ispytanie transformatorov maloy i sredney moshchnosti na napryazhenie do 35 kV vklyuchitel'no. [Voltage testing of smalland medium-power transformers up to including 35 kV.] Moscow: Energiya, 1969, 296 p. (in Russian).
5. Kish, L. Nagrev i okhlazhdenie transformatorov. [Heating and cooling of transformers.] Biki, M.A., transl. from Hungarian; Tarle, G.E., ed. Moscow: Energiya, 1980, 208 p. (in Russian).
6. Liu, J., Zhang, A.H. Transformer Simulation and Evaluation of Power Winding Short-circuit Dynamic Stability. Transformer, 2012, vol. 49, no. 6, pp. 14–25.
7. Kondrashova, Y.N., Khramshin, R.R., Nikolaev, A.A. , Shurygina, G.V. Analysis of thermal state of power transformer of captive power plant. Procedia Engineering, 2015, vol. 129, pp. 832–838.
8. German, L.A., Sharov, A.V. Сalculation of short-circuit currents in ac traction railroad networks. Electrical Technology Russia, 2003, no. 3, pp. 27–34.
9. Guy, A., Didenko, S. Automated calculation of short-circuit currents using software «elplek». Науковий вісник нубіп України. Серія: Техніка та енергетика АПК, 2014, no. 194-2, pp. 82-90.
10. Tian, M., Yang, D. Short-circuit reactances of a controllable reactor of multi-parallel branch type's influence on its branch reactances and currents. Diangong jishu xuebau, 2014, Vol. 29, no. 7, pp. 237–243.
Review
For citations:
Kostyukov A.V., Solomin V.A., Kostyukov A.A. Ensuring safe operating conditions for power transformers under thermal effects of short-circuit curre. Vestnik of Don State Technical University. 2018;18(1):132-137. (In Russ.) https://doi.org/10.23947/1992-5980-2018-18-1-132-137